So you want to open a restaurant, only to find there’s no way to exhaust your kitchen hood to the outside like a class 1 cooking restaurant. Maybe you’re a sushi restaurant that doesn’t have a hood and is considered class 5 cooking, but now you’d like to add some tempura to your menu.
It’s important to know the pros and cons to help you make your decision on whether to use a ventless hood that’s class 4 cooking, or a standard kitchen exhaust system that’s class 1 cooking.
What is standard kitchen exhaust?
A typical restaurant kitchen exhaust consists of four major components:
- Kitchen exhaust fan
- Hood
- Make-Up Air Unit
- Hood fire suppression
As you cook, the products of combustion rise up and become trapped within the hood—a process known as capture and containment. These products are then pulled through the grease filters, which remove most of the grease. Next, the exhaust enters the grease duct, travels up to the kitchen exhaust fan, and is expelled into the atmosphere. Simultaneously, a make-up air unit supplies the restaurant with fresh air to prevent negative pressure in the restaurant. You can read up on the importance of make-up air in another article on restaurant odours.
How ventless hoods work
Ventless hoods typically consist of a grease filter, pre-filter, high-efficiency filter, carbon filter, integral hood fire suppression, and a fan. A ventless hood first extracts the larger grease particles through the grease filter. The grease filter is much like the one in a typical class 1 hood. It uses centrifugal acceleration to remove the heavier grease particles. This grease then drains into a cup, which the restaurant operator empties manually. The pre-filter and high-efficiency filter remove the remainder of the grease particles by physically trapping them in their media. The carbon filter helps remove some of the odours.
Below is a diagram (courtesy of Wells) of a typical ventless hood and how it operates:
4 Stage Filtration
- Stage 1: Stainless steel baffle filter
- Stage 2: Fire rated pre-filter
- Stage 3: High-efficiency air filter
- Stage 4: Carbon/charcoal filter


The Pros and Cons of installing a Class 4 Ventless Hood
Pros
- Ease of installation as less construction is required when compared to class 1 cooking
- Cost savings due to no grease duct and external kitchen exhaust fan required
- Minimal construction time which allows you to open your doors sooner
Cons
- Only electric cooking appliances allowed, NO GAS. Typically, you need a minimum of 400amps on your electrical panel.
- There are strict parameters set out by the manufacturer that limit the kilowatt, temperature and dimensions of the cooking appliances. This means not every cooking appliance can be used.
- May be noisier than a standard kitchen exhaust system
- Odours and heat may remain within the restaurant, and nearby residents could complain if the exhaust is located close to operable windows.
- Still requires general exhaust and make-up air unit
In some cases, it is simply not practical or even possible to install a standard kitchen exhaust system. For example, if your restaurant is on the ground floor of a multi-storey building and you cannot exhaust out the front, back or up to the roof. In this case, it may be a good option to go ventless. However, you also need to consider whether you have enough electrical capacity and whether trapped odours, noise and elevated temperatures are acceptable in the restaurant.
In our experience, ventless hoods are a good option for a sushi restaurant that wants to add a 14″ fryer for tempura, or a restaurant that is mostly take-out, where odours have less impact on dine-in customer comfort.
If you have any questions, please don’t hesitate to reach out to us and we will help you find a suitable design solution for your space.
James Hicks, P.Eng.
Principal | Evolve Mechanical Solutions
236.777.3487