A poorly installed air conditioner can cost more than a repair bill. In this case, the risk was hanging above the alley.

A famous and very successful restaurant in Vancouver had a contractor install a split A/C.  The photo below shows the outdoor A/C unit suspended outside the restaurant in the back alley.

What Went Wrong

  • Circled in red: temporary mechanical clamps typically used for strapping down material in a flatbed truck.  These will rust and fail.
  • Exposure to the elements, particularly UV rays, will make the webbing brittle and cause it to fail.
  • The left-hand mechanical clamp is attached to a fire escape ladder, potentially hindering occupants’ escape in the event of a fire.
  • No seismic cabling to keep the outdoor A/C unit from falling during an earthquake.

Outdoor air-conditioning unit suspended beside a fire escape, with red circles identifying the strap clamps

The Risk Below

If this outdoor A/C unit falls, anyone in the alley below could be seriously injured or killed.

Hire qualified, reputable trades and engineers for your restaurant installations. Equipment needs proper support—not a shortcut that puts people below at risk.

James Hicks, P.Eng.
Principal | Evolve Mechanical Solutions
236.777.3487

#Fail #restaurant #HVAC