What we found within ten minutes of this 2016 inspection was frightening. Evolve Mechanical Solutions had been retained to inspect a very popular downtown Vancouver venue. The annotated photos below show what we found.
The kitchen and hood
The photograph shows the cooking lineup in the main kitchen. You’re probably wondering how an installation like this can pass inspection in a country with strict building by-laws.
What we find is that this construction takes place long after the inspectors, engineers and fire department sign off on the original building plan, which doesn’t include this kitchen. After a few months, the tenant decides to add a menu to their venue. Or perhaps they already serve soups and sandwiches but want to expand their menu to include hamburgers, fries, etc. The tenant then finds a contractor to install it, and the work proceeds without a building permit.
The photos below show the result.
The exhaust duct
The exhaust duct shown below was fastened to the hood with screws. Screws can be used if listed but should be used as a last resort. Welding is the preferred method as it is liquid tight and the large temperature ranges seen during the cooking operation allow for expansion and contraction of the hood and exhaust duct. Over time the screws may loosen with such large temperature ranges.
Since there were no grease filters on the hood grease built up on the exhaust duct allowing for the build up of combustible fuel for a fire. Further to this the duct appears to be standard sheet metal and not 16 gauge black iron which means it would melt away in minutes allowing the fire to spread. Whereas 16 gauge black iron would last substantially longer during a fire thus allowing the occupants to escape the premises before the fire spreads.


Electrical penetrations
The picture below shows electrical cords penetrating the hood. This can allow for the build up of grease in the cavity behind the hood. What makes this worse is the electrical cable could short and provide the means to ignite the fuel and cause a fire.
The system had been certified as clean, despite the deficiencies shown here. The contractor should tell the tenant that this operation is not to code and notify the city or fire department. These deficiencies put the tenant, customers and neighbours at risk. (The name, company and ASTTBC number have been blanked out.)


Rooftop exhaust
The kitchen exhaust fan on the roof showed more of the same. Probably not listed, no grease cup collection so grease is spewing onto the roof. Most concerning is the canopy, it’s laden with grease and one little spark could light it up thus causing a roof fire.
These problems were visible during a quick ten-minute walkthrough. Who knows what else we would have found by dismantling the installation and looking deeper.
At the time of our 2016 inspection, the venue was closed and we had informed the new tenants of the deficiencies. They were receptive and planned to upgrade the kitchen exhaust system to meet NFPA-96.
James Hicks, P.Eng.
Evolve Mechanical Solutions
236.777.3487